Z202025-0P PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / suppor[email protected] 03131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
G SERIES
INSTALLATION GUIDE
PRODUCT OVERVIEW
The G Series carbon monoxide detectors measure CO levels and signal control systems
to provide an inlet of fresh air optimal for the space at a given time. G Series devices
are equipped with a relay contact that closes when the CO level is below 25 ppm
and opens when the CO level is above 25 ppm (when used with a normally closed
contactor). Removal of the sensor, interruption of power, or cut wires cause the relay
circuit to open and start the fan. Minimum relay cycle time is 3 minutes to prevent
fan short-cycling.
Audible Alarm: An 85 dB alarm sounds if the CO level rises above 100 ppm for 30
minutes.
WIRING DIAGRAM
-
+
-
+
0-10V/0-5V
or
4-20mA
DDC
SYSTEM
V in
COMM
SENSOR
CONTACTOR
POWER
FAN
POWER
N.C.
CONTACTOR
ALARM
N.O.
OUT
SENSOR DETAIL
Common
Out 0-5V/10V or 4-20mA
IN V+ 15-30VDC, 24VAC
N.O. Relay
N.O. Relay
OUTPUT
10V
5V
PPM
100
200
TROUBLESHOOTING
Problem Solution
4-20 mA output does not function Verify that the unit is a 4-20 model.
Verify that the unit is wired for sourcing output.
Output is half or twice what is
expected
Verify span jumper is set to desired scale.
• For voltage units, verify jumper is set to desired
voltage output scale.
Output is inaccurate or unstable • Allow 96 hours for sensor to burn in and stabilize.
SERVICE
For any service or installation, consult qualied service personnel. To ensure
continued reliable operation, replace the sensor module every ve years with a Veris
Industries CO sensor replacement module (Veris part number AA09).
Replacement instructions:
1. Disconnect power from the unit.
2. Carefully remove the old sensor module.
3. Install the new module rmly into the socket.
4. Reconnect power to the unit.
5. The replacement sensor requires 96 hours to stabilize after initial power
application.
The sensor module is factory calibrated. No eld calibration is required or possible.
Verify proper operation by observing the LED indicators.