INSTALLATION GUIDE
Carbon Monoxide Transmitter
and Fan Controller
SPECIFICATIONS
Input Power 15-30VDC/24VAC, 0.3A@24VAC
Sensor Type Digitally proled Metal Oxide Semiconductor (MOS)
Sensor Life 5-10 years typical, replaceable
Detection Range 0 to 200 ppm
Analog Output 3-wire sourcing, 4-20mA or user selectable 0-5V/0-10V (specify mA or V)
Output Scaling User-selectable 100 ppm F.S. or 200 ppm F.S.
Response Time 2 min 30 sec sample interval cycle
Relay Output N.O. Form A (SPST) 8A@30VAC/VDC; (Use with N.C. contactor)
Relay Setpoint 25 ppm
High Limit Setpoint 100 ppm for 30 minutes
High Limit Alarm Audible, 85 dB, resets below 100 ppm (solid-state contact for -AS version)
High Limit Contact (-AS Models) 250VAC/DC, 120mA max. Ron 35 Ω
LED Indicators Solid Green = Normal; Solid Red = Call for ventilation;
Flashing Green = Sensor life has expired; Flashing Red = High-limit alarm
Operating Temperature Range -20° to 50°C (-4° to 122°F)
Operating Humidity Range 0 to 90% RH non-condensing
Coverage 5000 sq ft typical (465 sq m)
Housing White powder coat over steel
G SerieS
DIMENSIONS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
INSTALLATION
1. Lock out all power supplies prior to installation.
2. Select a location for the sensor in a secure area where it will be accessible only
to qualied service personnel. Install the G Series sensor centrally in the parking
structure, near the main trac paths, but away from outside air vents and
excessive drafts. Mount the unit securely to a wall or column at a height of about 5
ft. (1.52 m) from the oor.
3. Connect wiring as shown in the Wiring section. If using a voltage output model,
use the Output jumper to select 0-5 V or 0-10 V.
4. Apply power to the unit. A green LED on the circuit board indicates proper
operation of the power supply.
Coverage is not dependent on the sensor. Coverage is a function of the building structure and air
ow patterns. A minimum of one sensor for 5000 sq. ft. is recommended. Wide open areas where
the air is well mixed may require multiple sensors.
2.4"
(55 mm)
2.5"
(63 mm)
0.9" dia.
(22 mm)
4.5”
(114 mm)
4"
(102 mm)
5.0"
(127 mm)
G
D = Duct mount
W = Wall mount
Enclosure
Auxiliary Alarm Output Output
A = Auxiliary Contact
X = None
= StandardV = Field-selectable,
0-5/0-10VDC
M =4-20mA
R = Relay only
S